Does a 1 hour fire rated wall require a fire damper?

Does a 1 hour fire rated wall require a fire damper?

Q: Are fire dampers required in one-hour fire-rated walls if the facility is fully sprinkled? A: According to NFPA 90A (1999 edition), one-hour fire-rated barriers do not require fire dampers in fully ducted HVAC systems, unless the one-hour fire-rated barrier is a vertical shaft.

How do I choose a fire damper?

Select a fire damper and combination fire smoke damper with a 1½ hour rating for use with a wall, floor, or partition with a less than 3 hour fire resistance rating. If the wall, floor, or partition has a fire resistance rating of 3 hours or more, the damper must have a rating of 3 hours.

What UL 555?

The UL 555 Fire Damper test standard originated in 1966 to ensure fire dampers would function properly in fire conditions. The original standard has been revised several times to address new discoveries in fire protection and developing technology since 1966.

What is a Type B fire damper?

Type-B Fire Damper: Used when airflow or velocity in the duct is a concern. The stack of blades in the fire damper frame is kept out of the air stream. Compared to an Type-A damper, the total square inches of free area in a Type-B damper is increased and the pressure drop is reduced.

Do you need a fire damper in a 30 minute wall?

Fire-resisting ducts are required to have a minimum fire resistance of 30 minutes (integrity).

Are fire dampers a legal requirement?

Under the Regulatory Reform (Fire Safety) Order it is a legal requirement to test fire dampers at regular intervals in accordance with fire safety in the design, management and use of buildings code of practice (BS:9999 2017), using a method known as ‘drop testing’.

How do you size a fire damper?

– Type A, E, and F Damper Overall Width = Duct Opening/Nominal Size – 1/4″ – Type B Damper Overall Width = Duct Opening/Nominal Size – 1/4″ – Type C Damper Overall Width = Duct Opening/Nominal Size +2″ – All fire dampers are available in 1/4″ increments.

What are the types of fire dampers?

There are two types of fire damper closing system: those with a fuse mechanism and those with an actuator, which is motorised, and to which you can connect a smoke detection system. There are also two fire classes for dampers: E-class or EI-class.

What is NFPA 90A?

NFPA 90A covers construction, installation, operation, and maintenance of air conditioning and ventilating systems, including filters, ducts, and related equipment, to protect life and property from fire, smoke, and gases resulting from fire or conditions having manifestations similar to fire.

When should fire dampers be installed?

Generally, fire dampers are required where air ducts penetrate walls that are rated for 2-hours or more. They are needed in all air transfer openings (non-ducted) in rated walls, regardless of the rating. And they are required at some, but not all penetrations of rated floor assemblies and shaft enclosures.

How long do fire dampers last?

This gives guidance for the two main types of fire damper: spring operated fire dampers should be drop tested, cleaned and maintained at intervals of no greater than 12 months; while all other models should be drop tested, cleaned and maintained at least every two years.

https://www.youtube.com/watch?v=YbSXsy0tPeM